                      | Search: |   
                    
                     
                   | 
                 
                    
				  
                  
                
                             
             | 
            
              | 
            
              
                
                  
  
    
    
    	| 
		
    		SCM202 AC Voltage to 4-20mA Converter | 
        
                (Up) | 
            
      
    
	
    
    
    
      
             
        
       | 
       | 
      
      The SCM202 measures AC voltage in the 0-500V range and converts it into a 4-20mA Current Loop signal. The unit also features galvanic isolation on both the input and output sides, and test points for monitoring the current loop without interrupting it. | 
     
    | 
        
        
        
     | 
      
   
 |  
                
 |  
    
  
                  
    Technical Specifications
    
      | Accuracy | 
      ±0.1% over full range, typical (for 2-100%) for sinusoidal input | 
     
    
      | Temperature stability | 
      ±0.02%/°C | 
     
    
      | Response time | 
      220 ms (0-98%) | 
     
    
      | Output voltage ripple | 
      0.1% of full range RMS | 
     
    
      | Frequency range | 
      40-500Hz | 
     
    
      | Galvanic isolation | 
      2.5KV RMS in 1 minute | 
     
    
      | Loop power supply | 
      10-32VDCc | 
     
    
      | Output current | 
      4-20mA | 
     
    
      | Test tap | 
      40-200mV represents 4-20mA (shunt 10ohm ±1%) | 
     
    
      | Output over-voltage protection | 
      33V tranzorb | 
     
    
      | Output over-current protection | 
      slow fuse 100mA 20x5mm | 
     
    
      | Current loop resistance | 
      Rmax(ohms)=(Vsupply-10)/0.02 | 
     
    
      | Zero adjustment | 
      ±25% min | 
     
    
      | Span adjustment | 
      ±25% min | 
     
    
      | Operating temp. range | 
      0-70°C without condensation | 
     
    
      | Storage temp. range | 
      -25 to 85°C | 
     
    
      | Enclosure | 
      plastic 35x89x71mm, IP50 | 
     
    
      | Mounting | 
      standard 35mm rail | 
     
 
  
        
                
    
      
                
        
                
       
    
                  	
                     
                 |  
               
             |